  • HW Series 1kva 2kva 3kva outdoor online UPS

    HW Series 1kva 2kva 3kva outdoor online UPS

    HW Series Brief introduction:
    HW series outdoor base station special online outdoor UPS system, is the global newest period control component and more advanced software perfect combine full intelligent digital product.
    Type : HW Series
    Phase : three phase
    Power Factor : 0.95
    Input voltage : 220/380V+/-25%
    Input frequency : 50/60Hz+/-10%
    INQUIRY DOWNLOAD PDF Format
    Details
    Features
    Parameters

    HW Series Brief introduction:


    HW series outdoor base station special online outdoor UPS system, is the global newest period control component and more advanced software perfect combine full intelligent digital product. That series product uses the six generator low-loss large power IGBT and static switch to be power component, it fully adopt digital control technique with available online programmable high speed microprocessor(MCU), and it is the perfect performance in digital electric technique.

    HW series UPS capacity range from 1KVA-3KVA, can extend to 20KVA, with 100% suitable grid environment, widely used in communication industry, outdoor communicate station.


    HW Series Main Features:


    • Advanced digital electric system super stable operation

    • Battery intelligent management, durable and free from worry, extend usage of battery over 55%

    • Intelligent detection system whole protection

    • Intelligent communicate tool remote control: RS232 and RS485, optional SNMP card or dry contacts

    • Adopt high precision SMD technique, whole machine highly precision

    • Basic with life period evaluate precise research, more save energy

    • Basic on six generation IGBT and high speed static switch transform technique, high reliability.

    • Super LED & LCD screen information processing technology, no restrict between user and UPS.

    • Super adapt to the reliability of the environment: characteristic under a harsh environment, stronger waterproof, dustproof, antifreeze, heat insulation and function makes it more reliable safety.

    • Super load characteristics: suitable from 0%-100% load jumping, and no need to changed to bypass, and protect output stable.

    • Perfect protection function

    • Optional battery circuit module

    • Optional input harmonic filter

    • Personalized Settings: can choose UPS working patterns, ECO energy conservation work patterns, EPS work patterns.


    MODELHW-1KHW-2KHW-3K
    Capacity1kVA2kVA3kVA
    Power Watt0.8kW1.6kW2.4kW
    Working PrincipleLow Freuqency  Transformer Based True On Line-Double Conversion
    RECTIFIER (INPUT)
    PhaseSingle Phase
    Input Voltage Range220VAC (230VAC or 240VAC)±25% , 1P+N+PE
    Input Frequency Range50Hz±10% / 60Hz±10% (Selectable)
    Output Ripple<2%
    Soft Start0~100% 5sec
    CHARGING
    Charging ModeConstant current, then constant voltage, and charge with temperature compensation                                                            
    Float Charging Voltage55VDC
    Equalized Charging Voltage56.8VDC
    Temp. Compensated Voltage-3mV/℃/cell
    Charging Current5-10A
    BATTERY
    TypeVRLA/AGM/Gel, optional Lithium Battery
    Battery Capacity7~200AH settable ( Configurate Battery Capacity according to Back-up Time )
    Quantity4units 12V or 24units 2V batteries   ( Battery Voltage 48VDC)
    Temperature20oC~25oC (For Maximum Efficiency)
    INVERTER (OUTPUT)
    PhaseSingle Phase
    Nominal Voltage220VAC (230VAC or 240VAC), 1P + N
    Output Voltage Regulated Accuracy±1 %( Stable load), ±3%( fluctuant load)
    Output Frequency Range50Hz 60Hz<±0.5% ( Asynchronous )
    Crest Factor> 3:1
    Output Total Harmonic Distortion (THD)Pure Sine Wave, Linear Load < 3%, Non-Linear Load<5%
    Dynamic CharacteristicsInstant voltage<±5% ( from 0 to100% ), Instant recover time<10ms
    Overload CapacityAt 115% load, normal work, At 125% load 10 min, At 150% load 1min
    Inverter Efficiency>93% ( full load )
    BYPASS
    PhaseSingle Phase ( P+N )
    Nominal Voltage220VAC (230VAC or 240VAC)
    Transfer Time0ms( adopt static switch )
    PROTECTION FUNCTION
    Input ProtectionInput voltage, frequency over limited protection
    Output ProtectionOver current, short circuit, over voltage, low voltage
    Battery ProtectionOver charge, over-discharge protection
    Temperature ProtectionEnvironment over temperature protection, inverter over temperature protection
    Hardware Fault ProtectionAssistant power abnormal, breaker cut off, breaker overload, power devices over current/over voltage etc. protection
    GENERAL SYSTEM PARAMETERS
    Working EnvironmentTemp: -25~55oC, relative humidity: 30%~90%, Altitude<2000m ( 1% decrease against 100 meters’ rise, Max. altitude 4000m )
    Cooling MethodCOMPULSIVE VENTILATION
    Communitation InterfaceRS232/ RS485, optional dry contact, SNMP card ( for remote control via internet )
    Auti-surge Capacity10/700μS, 5KV;  8/20μS, 20KA
    Protection LevelIP43
    Safety PerformanceVin-n Vout-n 2000Vac, creepage<10mA , insulating resistance>2MΩ(500VDC)
    Noise (dB)45~50
    Dimension (W*D*H) mm890*640*1250 (Max. built-in 8PCS12V100Ah Batteries
    Weight (Kg)105115135